Digital pressure transmitter with oil-free ceramic sensor for measurement in gases or liquids





Specs at a glance
-
Accuracy
Standard 0.1%
Platinum 0.075% -
Process temperature
-20°C…130°C
(-4°F…266°F) -
Pressure measuring range
100 mbar…40 bar
(1.5psi…600psi) -
Process pressure / max. overpressure limit
60 bar (900 psi)
-
Main wetted parts
Ceraphire
Sealing
Alloy C276
316L -
Max. measurement distance
400 m (1312 ft) H2O
-
Material process membrane
Ceramic
-
Measuring cell
100 mbar…40 bar
(1.5 psi…600 psi)
relative/ absolute
Field of application
The Cerabar PMC51 is a digital pressure transmitter featuring a capacitive, oil-free ceramic measuring cell. It is commonly used in process and hygienic applications for measuring pressure, level, volume, or mass of liquids and gases. The vacuum-proof ceramic membrane with integrated breakage detection ensures a high degree of system safety. The Quick Setup with adjustable measuring range allows for simple commissioning, reducing costs and saving time. The Cerabar PMC51 is SIL2 certified according to IEC 61508 and IEC 61511.
Single chamber aluminum or stainless steel (316L) housing.
-
Process connections: Threads, flanges or hygienic connections
-
Process temperature: -40 to +130°C (-40 to +266°F), 150°C (302°F) for 1h
-
Measuring ranges: -1/0 up to +40bar (-15/0 to +600psi)
-
Accuracy: ±0.1%, “Platinum” ±0.075%
-
International explosion protection certificates, SIL, hygienic approvals, marine approvals
Benefits
-
Best fit for vacuum applications and applications with corrosive and abrasive media
-
Process safety through membrane breakage detection
-
Overload-resistant high purity ceramic sensor (99.9% Al2O3)
-
Condensation resistant also for hygienic applications
-
Easy menu-guided commissioning via local display, 4 to 20mA with HART, PROFIBUS PA, FOUNDATION Fieldbus
-
Process pressure up to SIL2, certified to IEC 61508 and IEC 61511
-
Available with mounted manifolds: always fit, always tested for leaks
Specifications
-
Characteristic
Smart and reliable pressure transmitter with capacitive measuring cell and ceramic process isolating diaphragm Ceraphire)
-
Supply voltage
4…20 mA HART
11,5…45V DC (Non Ex):
Ex ia: 11,5…30V DC
PROFIBUS PA:
9…32 V DC (Non Ex)
FOUNDATION Fieldbus:
9…32 V DC (Non Ex) -
Reference Accuracy
Standard 0.1%
Platinum 0.075% -
Long term stability
0.2% of URL/ year
0.4% of URL/ 5 years
0.5% of URL/ 10 years -
Process temperature
-40°C…+130°C
(-40°F…+266°F
+150°C for 1h
(+302°F for 1h) -
Ambient temperature
-40°C…+85°C
(-40°F…+185°F) -
Measuring cell
100 mbar…40 bar
(1.5 psi…600 psi)
relative/ absolute -
Smallest calibratable span
10 mbar (0.15 psi)
-
Vacuum resistance
0 mbar abs.
-
Max. Turn down
20:1
-
Max. overpressure limit
60 bar (900 psi)
-
Process connection
Thread:
G1/2…G2, R1/2, MNPT1/2
Flange:
DN25…DN80,
ASME 1″…4″,
JIS 10K -
Process connection hygienic
Tri-Clamp
DIN11851
DIN11864-1
NEUMO
Varivent N
SMS
DRD -
Material process membrane
Ceramic
-
Material gasket
Viton, EPDM, NBR, Kalrez
-
Fill fluid
None, dry measuring cell
-
Material housing
Die-cast aluminum,
AISI 316L -
Communication
4…20 mA
4…20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
IO-Link -
Certificates / Approvals
ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, UK Ex
-
Safety approvals
SIL
-
Design approvals
EN10204-3.1
NACE MR0175 -
Hygienic approvals
CoC ASME-BPE
3A, EHEDG -
Marine approvals
GL/ ABS/ LR/ BV/ DNV
-
Drinking water approvals
NSF
-
Successor
PMC51B